iTrans™ Specifications
 
Enclosure

Cast aluminum, poly-bonded coating, explosion-proof, NEMA 4X, IP66 rating

 
Sensors:

Combustible Gases: Catalytic bead and/or Non-Dispersive
Infrared (NDIR) Oxygen / Toxic Gases: Electrochemical diffusion

 
Ranges:

Combustible gases: 0 -100% LEL in 1% increments
Hydrogen: 0 - 1999 ppm in 1 ppm increments
Oxygen: 0 - 30.0% by volume in 0.1% increments
Ammonia: 0 - 200 ppm in 1 ppm increments
Carbon Monoxide: 0 - 999 ppm in 1 ppm increments
Hydrogen Sulfide: 0 - 500 ppm in 1 ppm increments
Sulfur Dioxide: 0.2 - 99.9 ppm in .01 ppm increments
Hydrogen Cyanide: 2 - 30 ppm in 1 ppm increments
Hydrogen Chloride: 0.2 - 30.0 ppm in .01 ppm incr.
Phosphine: 0 - 1.00 ppm in .01 ppm increments
Nitrogen Dioxide: 0.2 - 99.9 ppm in 0.1 ppm increments
Nitric Oxide: 0.0 - 99.9 ppm in 0.1 ppm increments
Chlorine: 0.2 - 99.9 ppm in .01 ppm increments
Chlorine Dioxide: .02 - 1.00 ppm in .01 ppm increments

 
Display:

Dual-channel split-screen LED display (4 digit, 7 segment arrangement per channel) provides simultaneous display of one or two gases.

 
Input Voltage:
12-28 VDC operating range (24 VDC typical)
 
Input Current (max.):

Toxic Gas / Oxygen: 150 mA @ 24 VDC (single gas)
Combustible gases (Catalytic): 175 mA @ 24 VDC, 0.6
A peak (single gas)
Combustible gases (Infrared): 150 mA @ 24 VDC, 0.6
A peak (single gas)
Combined catalytic/infrared: 280 mA @ 24 VDC (two gas)

 
Signal Output:

4-20 mA, linear analog) and ModBus RTU (digital)
RS485 digital communication with ModBus RTU
software protocol system at 9600 baud. Three or four
wire system capable of accommodating over 200
devices in bus configuration. Address selection
through on-board 8-position dipswitch.

 
Alarm Relays:

3 alarm relays: Fault, plus 2 user-programmable
relays, SPST, NO or NC (relay-option versions)

 
Contact Capacity:

5 Amps @ 30 VDC

 
Temperature Range:

-4°F to +104°F (-20°C to +40°C), typical
-40°F to +167°F (-40°C to +75°C) - Catalytic LEL

 
Humidity Range:

15-90% RH (non-condensing), typical

 
 
APPROVALS

NRTL/c: Class I, Div. 1, 2, Groups B, C, D
CSA: Class I, Div. 1, 2, Groups B, C, D
CENELEC (ATEX): EEx d IIB
Australia: EEx d IIC T4
China: GB 3836.1-Ex d IIC T4; LEL version
GB15322-94 Fire protection
India: CCoE - Nagpur

 
 
 
 

 


 

 