Enclosure |
 |
|
NEMA 1 General
purpose indoor use,
electroplated for
RFI protection Wall
mounted, two screw
placement |
|
|
|
Dimensions and
Weight |
|
7.2" x 5.6" x 1.6"
(18.29 cm x 14.22 cm
x 4.06 cm)
17 oz (482 g) |
|
|
|
Weight |
|
Push button alarm
silence, calibration
and fresh air zero –
no tools needed |
|
|
|
Sensor Type |
|
Electrochemical |
|
|
|
Measuring Ranges |
|
Ammonia - 0 to 100
ppm
Carbon Monoxide,
Hydrogen Sulfide -0
to 999 ppm in 1 ppm
increments
Chlorine, Nitrogen
Dioxide, Sulfur
Dioxide -0 to 99.9
ppm in 0.1 ppm
increments
Oxygen - 0 to 30%
volume in 0.1 %
increments |
|
|
|
Display |
|
3 1/2 digit, high
resolution LED |
|
|
|
Power |
|
12-24 VDC with
supplied120 VAC,
plug in adapter
|
|
|
|
Alarms |
|
Visual: Ultra-bright
LED, Amber-Low,
Red-High
Audio: 83db at 3
meters |
|
|
|
Temperature Range |
|
-4° to 122°F (-20°
to 50°C) |
|
|
|
Humidity Range |
|
Ammonia, Carbon
Monoxide, Chlorine,
Hydrogen Sulfide,
Nitrogen Dioxide,
Sulfur Dioxide - 15%
to 90%
Oxygen - 0% to 99% |
|
|
|
APPROVALS |
|
CSA C22.2 No. 205-M
1983
CE (pending) |